Product Details
WBI412F31-50A-500A input AC Current Sensor(500A Max) converts AC input current into a load independent output signal DC voltage 0-5V,0~10V. It has adopted electromagnetic isolation principle for real time measurement of AC current from electric net or electric circuit. The output signal (voltage or current) of this transducer is proportional to the rectified average value of input AC current or reflects the input current wave. They are suitable for general applications such as fixed frequency voltage supplies etc.
Specifications:
Rated input current AC |
50A, 100A, 200A, 300A, 400A, 500A AC |
Output signals |
0-5(10)V DC |
Accuracy |
0.2% |
Input impedance |
measuring current<100mA, input impedance 200Ω;
measuring current ≥100mA, input impedance approximate zero
|
Responding time |
300ms |
Linear measuring range |
0 - 1.2 times of rated input current |
Over load capacity |
30 times of rated input current, 5s |
Frequency range |
25Hz~5kHz |
Output impedance |
5mA |
Static current |
5mA |
Power supply |
+12V/+15V/+24V DC |
Isolation voltage |
≥2500Vdc, for 1 minute |
Output ripple |
<6mV |
Thermal drift |
350ppm/°C |
Ambient temperature |
-10℃~+50℃ |
Mounting type |
DIN rail 35mm mount or screw mount |
Material of shell |
ABS (According to UL94V-0) |
Protection of shell |
IP20 |
Shell type |
with aperture Ф35mm |
MTBF |
>50000h |
Dimensions (mm)
Dimensions: 107x 24 x 60mm, Aperture: Ø35 mm
Pin Arrangement:
+: V+
-: V- (or NC)
GND: Ground of power supply and output
OUT: Output
|
Advantages:
High precision,
High isolation,
Low power consumption,
Low drift,
Wide temperature range,
Anti-interference,
Strong ability,
Wide working power range.
|
http://www.wbsensor.com/